Clean room HVAC controls airborne particles, pressure, temperature and humidity. It uses AHUs with multi-stage filtration and terminal HEPA filters, high air change rates and a pressure cascade (commonly 10 to 15 Pa between adjacent rooms) so air flows from cleaner to less clean areas. Systems are designed to ISO 14644 and GMP requirements.
Clean room classes
Clean rooms are classified by how many airborne particles they allow. ISO 14644-1 sets the limits; pharma GMP grades map onto them.
| ISO class | Max particles ≥ 0.5 µm per m³ | EU GMP grade (approx.) | Typical use |
|---|---|---|---|
| ISO 5 | 3,520 | Grade A; Grade B at rest | Aseptic filling zones, under laminar air flow |
| ISO 6 | 35,200 | Not used in EU GMP | Electronics, some medical devices |
| ISO 7 | 352,000 | Grade C at rest; Grade B in operation | Sterile preparation, background to Grade A |
| ISO 8 | 3,520,000 | Grade D at rest; Grade C in operation | Oral solid dosage, packing, support areas |
How clean room HVAC works
- Multi-stage filtration: pre-filter and fine filter in the AHU, and terminal HEPA filters (H13 at 99.95%, H14 at 99.995% efficiency at the most penetrating particle size) at the room supply.
- High air change rates to dilute and remove particles, set by the room class and the process.
- Low-level return air so air sweeps particles down and out of the room.
- Pressure cascade so air always flows from cleaner rooms to less clean ones.
- Temperature and humidity control to the product's and operators' requirements.
- Airlocks (cascade, bubble or sink types) between zones of different class.
Pressure cascade
A pressure cascade keeps contamination out of critical rooms. Steps of 10 to 15 Pa between adjacent rooms are common; actual values come from the facility's design.
Where clean room HVAC is needed
Pharma formulations and APIs, biotech and vaccine labs, hospital operation theatres and ICUs, medical devices, food and nutraceuticals, electronics and research labs.
Our clean room HVAC scope
- Study of the user requirement specification (URS), room data sheets and process layout
- Heat load, air change and air balance calculations per room
- Zoning, pressure cascade and airlock concept
- AHU selection with filtration stages, HEPA terminal boxes and return risers
- Ducting with insulation, volume control dampers and differential pressure gauges
- Installation, air balancing and commissioning
- Support for testing: air velocity and air changes, HEPA filter integrity, particle count and recovery, coordinated with validation agencies
- AMC with filter monitoring and periodic re-testing support
Standards we design with
Our pharma and healthcare clients include Relax Biotech, Fermenta Biotech, Osaka Pharmaceutical, Ayurlab Herbals, Puronutra Healthcare and Bajaj Healthcare.
Frequently asked questions
What is clean room HVAC?
Clean room HVAC is an air system that controls airborne particles, room pressure, temperature and humidity. It uses AHUs with multi-stage filtration, terminal HEPA filters, high air change rates and a pressure cascade between rooms.
What is the difference between ISO 7 and ISO 8 clean rooms?
An ISO 7 room allows up to 352,000 particles of 0.5 µm or larger per cubic metre, while ISO 8 allows up to 3,520,000. ISO 7 therefore needs more air changes and tighter control than ISO 8.
Why is pressure differential important in a clean room?
Keeping cleaner rooms at higher pressure than adjacent areas makes air flow outward through doors and gaps, so contaminated air cannot enter. Steps of 10 to 15 Pa between adjacent rooms are common.
What is the difference between H13 and H14 HEPA filters?
Under EN 1822, H13 filters capture at least 99.95% and H14 filters at least 99.995% of particles at the most penetrating particle size. H14 is used for the most critical areas.
How often should a clean room be tested?
Clean rooms are re-tested periodically as defined by the facility's quality system and ISO 14644-2, typically at least once a year for classification, with ongoing monitoring between tests.