Industrial · AHU

Air handling units (AHU)

Double-skin, treated fresh air and hygienic AHUs with the right filtration for each application.

Pipes and mechanical services inside a building
Quick answer

An air handling unit (AHU) filters, cools or heats, dehumidifies and circulates air through ducting. AHUs work with chillers or DX units in large buildings, hospitals, factories and clean rooms. Types include double-skin AHUs, treated fresh air (TFA) units, hygienic pharma AHUs and fan coil units.

What is inside an AHU

Air handling unit sections in order: mixing box, pre-filter, fine filter, cooling coil, heating coil and supply fan, followed by ducting and HEPA terminal filters for clean rooms AHU casing · double-skin insulated panels Mixing boxfresh + return Pre-filterG4 Fine filterF7 to F9 Cooling coilDX / CHW Heating coilreheat Supply fanEC / belt Ducting+ HEPAclean rooms air flow

Typical section order. The exact build depends on the application; clean rooms add terminal HEPA filters.

SectionWhat it does
Mixing box and dampersBlends fresh outdoor air with return air in the right proportion
Pre-filter (G4)Captures coarse dust and protects the coil and fine filters
Fine filter (F7 to F9)Removes fine particles for offices, hospitals and pharma
Cooling coilCools and dehumidifies the air, using chilled water or refrigerant (DX)
Heating or reheat coilControls humidity and temperature where required
Supply fanMoves the air through ducting against the system's static pressure
HEPA filters (H13 / H14)Final filtration at the room terminals for clean rooms

Types of AHU we supply and install

Double-skin AHUSandwich panels with insulation for low heat gain and no condensation on the casing. The standard for commercial and industrial use.
Treated fresh air unit (TFA / FAHU)Filters and pre-cools 100% outdoor air before it enters the building, improving indoor air quality and reducing load on room units.
Hygienic / pharma AHUSmooth internal surfaces, multi-stage filtration and drainable sections for clean rooms, OTs and labs.
Ceiling-suspended and floor-mounted AHUsCompact units above ceilings for smaller zones, or floor-mounted units in AHU rooms for larger air quantities.
Fan coil units (FCU)Small chilled-water units for individual rooms in hotels, hospitals and offices.

AHU vs FCU

AHUFCU
SizeLarge, serves a zone or floorSmall, serves one room
Fresh air and filtrationFull control, multi-stage filtersLimited
DuctingExtensiveShort or none
Typical useHalls, wards, production areas, clean roomsHotel rooms, cabins, patient rooms

How we select an AHU

  • Air quantity (CFM) from heat load and air-change requirements
  • External static pressure of the duct system and filters
  • Cooling capacity, coil rows and face velocity
  • Fresh-air percentage and filtration level for the application
  • Space for the unit, access for maintenance, and noise limits

AHU maintenance

Filter pressure-drop checks and cleaning or replacement, coil and drain-pan cleaning, fan belt and bearing checks, damper and control checks. Under an AMC, we log readings so problems show up before they affect the space.

See photos from our projects

Frequently asked questions

What is an AHU in HVAC?

An AHU (air handling unit) is a large unit that filters, cools or heats, dehumidifies and circulates air through ducting. It works with a chiller or DX outdoor unit and is used in large buildings, hospitals, factories and clean rooms.

What is the difference between an AHU and a TFA unit?

A normal AHU mixes return air with some fresh air. A TFA (treated fresh air) unit handles 100% outdoor air, filtering and cooling it before supplying it to the building or to other AHUs.

What is a double-skin AHU?

A double-skin AHU has casing panels made of two metal sheets with insulation between them. This reduces heat gain and noise and stops condensation forming on the outside of the unit.

Which filters are used in a pharma AHU?

Pharma AHUs typically use a pre-filter (G4), a fine filter (F7 to F9) and terminal HEPA filters (H13 or H14) at the room supply, depending on the clean room class.