An air handling unit (AHU) filters, cools or heats, dehumidifies and circulates air through ducting. AHUs work with chillers or DX units in large buildings, hospitals, factories and clean rooms. Types include double-skin AHUs, treated fresh air (TFA) units, hygienic pharma AHUs and fan coil units.
What is inside an AHU
Typical section order. The exact build depends on the application; clean rooms add terminal HEPA filters.
| Section | What it does |
|---|---|
| Mixing box and dampers | Blends fresh outdoor air with return air in the right proportion |
| Pre-filter (G4) | Captures coarse dust and protects the coil and fine filters |
| Fine filter (F7 to F9) | Removes fine particles for offices, hospitals and pharma |
| Cooling coil | Cools and dehumidifies the air, using chilled water or refrigerant (DX) |
| Heating or reheat coil | Controls humidity and temperature where required |
| Supply fan | Moves the air through ducting against the system's static pressure |
| HEPA filters (H13 / H14) | Final filtration at the room terminals for clean rooms |
Types of AHU we supply and install
AHU vs FCU
| AHU | FCU | |
|---|---|---|
| Size | Large, serves a zone or floor | Small, serves one room |
| Fresh air and filtration | Full control, multi-stage filters | Limited |
| Ducting | Extensive | Short or none |
| Typical use | Halls, wards, production areas, clean rooms | Hotel rooms, cabins, patient rooms |
How we select an AHU
- Air quantity (CFM) from heat load and air-change requirements
- External static pressure of the duct system and filters
- Cooling capacity, coil rows and face velocity
- Fresh-air percentage and filtration level for the application
- Space for the unit, access for maintenance, and noise limits
AHU maintenance
Filter pressure-drop checks and cleaning or replacement, coil and drain-pan cleaning, fan belt and bearing checks, damper and control checks. Under an AMC, we log readings so problems show up before they affect the space.
Frequently asked questions
What is an AHU in HVAC?
An AHU (air handling unit) is a large unit that filters, cools or heats, dehumidifies and circulates air through ducting. It works with a chiller or DX outdoor unit and is used in large buildings, hospitals, factories and clean rooms.
What is the difference between an AHU and a TFA unit?
A normal AHU mixes return air with some fresh air. A TFA (treated fresh air) unit handles 100% outdoor air, filtering and cooling it before supplying it to the building or to other AHUs.
What is a double-skin AHU?
A double-skin AHU has casing panels made of two metal sheets with insulation between them. This reduces heat gain and noise and stops condensation forming on the outside of the unit.
Which filters are used in a pharma AHU?
Pharma AHUs typically use a pre-filter (G4), a fine filter (F7 to F9) and terminal HEPA filters (H13 or H14) at the room supply, depending on the clean room class.
Last updated: